Industry background. As liquid cooling spreads through AI data centres, the cooling distribution unit (CDU) has become one of the most discussed components. A CDU sits between the facility water system and the rack-level liquid loop, regulating coolant temperature and flow before it reaches the cold plates.
The three core components
- Cold plate – mounted directly on the heat-generating component, transferring heat into the coolant.
- Manifold – distributes coolant to each cold plate in the rack and collects the return flow.
- CDU – regulates temperature, pressure and flow for the rack loop, typically separating a primary facility loop from a secondary equipment loop.
Why the control loop matters
The CDU's job is to hold secondary-loop supply temperature steady. If it drifts upward, chips throttle; if the control is crude, pumps cycle on and off, which wastes energy and wears equipment. Both outcomes argue for closed-loop PID control with tunable parameters rather than simple on/off switching.
What to monitor
Practical installations monitor supply and return coolant temperature, differential pressure across filters and heat exchangers, loop pressure, and room temperature and humidity – the latter against ASHRAE guidance of roughly 20–25 °C and 40–60% RH.

From a real project panel: a QSP-400B gateway collecting plant-room measurements for the BMS — the point where CDU monitoring data joins the building system.