P-IOM633 Programmable I/O Module | BACnet MS/TP & Modbus RTU, Built-in PID Control, 6 AI / 3 AO / 6 DI / 3 Relay
P-IOM633 programmable I/O module for BAS, HVAC and industrial control: 6 universal inputs (0-10 V / 4-20 mA / NTC-10K / dry contact), 3 analog outputs, 6 digital inputs, 3 relay outputs, built-in PID control, BACnet MS/TP or Modbus RTU and web configuration. OEM/ODM supported.
P-IOM633 is a DIN-rail programmable I/O module that combines remote I/O acquisition with local programmable control. Built on the proven IOM-633 hardware platform with expanded MCU flash and rewritten firmware, it adds built-in PID closed-loop control, a web configuration interface and Function Block programming, so building automation, HVAC and industrial projects can close the control loop inside the module - without an extra controller or a dedicated host computer. Modbus RTU and BACnet MS/TP models are available for direct integration with BMS, PLC and DCS systems.
Key Features
- Built-in PID control - setpoint SP, proportional gain Kp, integral time Ti, derivative time Td, dead zone, output bias, direct/reverse action and output limits Ymin/Ymax for stable temperature, pressure and flow loops.
- Up to 16 programmable Function Blocks - PID, Scale, High Select, Low Select, Two-Position, Compare, AND, OR, NOT, Delay and Buffer, executed on a 100 ms scan cycle; local interlocks and coordinated control without adding a PLC.
- 6 universal inputs (UI1-UI6) - every channel independently selectable as 0-10 V, 4-20 mA, NTC-10K or dry contact with a 12-bit ADC; channels set to dry contact work as 6 digital inputs with 20 ms debounce.
- 3 analog outputs (AO1-AO3) - 0-10 V or 4-20 mA, 0.1 % resolution, 10-step soft start and MAN/AUTO manual override, for valves, damper actuators and VFD-driven pumps.
- 3 relay outputs (BO1-BO3) - independent passive relay contacts with no common terminal, LATCH or 100 ms PULSE mode, for fans, pumps and alarm circuits.
- 32 internal points (N1-N32) - floating-point or logic variables passed between Function Blocks or exchanged with the master station.
- Fieldbus options - Modbus RTU slave (9600-115200 bps) or BACnet MS/TP master node (76800 bps); BACnet Device, Analog Input, Analog Output, Binary Input and Binary Output objects are supported.
- Browser-based configuration - double-click the RST key to enter configuration mode, connect the RS485 port through a USB-RS485 adapter with the PC at 192.168.5.1, then open http://192.168.5.2/ to set channels, bus parameters and Function Blocks; firmware can be upgraded online - no dedicated software needed.
- Reliable on site - complete isolation between power, communication and relay outputs, power-loss save of all parameters, built-in watchdog (auto reset), 500 V DC dielectric withstand, status LEDs plus a 5-bit address LED, and one-button factory reset.
Applications
- Building automation (BAS/BMS) - remote I/O and local closed-loop control for AHUs, chillers and terminal units.
- HVAC - temperature and humidity loops, air/water valve regulation, fan interlock and anti-short-cycle control.
- Data centre liquid cooling (CDU) - PID control of coolant temperature, secondary-loop pressure and pump/valve actuators.
- Industrial control - analog and digital acquisition, actuator control and interlocking on PLC, DCS and SCADA sites.
- Energy management - metering, monitoring and on-site logic where a full controller is not justified.
Models and Ordering
| Model | Fieldbus | Bus role | Default address |
| PIOM-633-M | Modbus RTU | Slave | 1 (range 1-247) |
| PIOM-633-B | BACnet MS/TP | Master node | MAC 1 (range 0-127) |
The communication protocol is fixed at the factory according to the model; please confirm the required model when ordering.
Technical Specifications
| Universal Input (UI1-UI6 / terminals I1-I6) | |
| Channels | 6, each independently configurable |
| Operating modes | 0-10 V / 4-20 mA / NTC-10K temperature / Dry Contact |
| Resolution | 12-bit ADC |
| Measurement range | 0-10 V; 4-20 mA (499 ohm sense resistor); NTC-10K -55 ~ +250 degC |
| Accuracy | 0-10 V: <= +/-0.8 % FS; 4-20 mA: <= +/-1.5 % FS; channel consistency <= 0.2 % FS |
| Over-range | The reading holds the last valid value |
| Analog Output (AO1-AO3 / terminals M1-M3) | |
| Channels / mode | 3, 0-10 V or 4-20 mA, independently configurable |
| Resolution | 0-1000 (0.1 % of full scale), 12-bit PWM |
| Accuracy | <= +/-0.8 % FS (0-10 V) |
| Control | Function Block (AUTO) or manual override (MAN), 10-step soft start |
| Digital Input and Output | |
| Digital input | 6 channels, shared with UI1-UI6 in DRY mode, dry contact, 20 ms debounce, high active |
| Relay output | 3 channels (D1-D3 / Q1-Q3), independent passive contacts with no common terminal, LATCH / PULSE (100 ms default), MAN/AUTO |
| Internal points | N1-N32, floating-point or 0/1 logic, readable and writable over the bus |
| Communication and System | |
| RS485 | Two-wire, 1 channel (A/B), automatic direction control |
| Baud rate | 9600 / 19200 / 38400 / 57600 / 76800 / 115200 bps |
| Data format | 7 or 8 data bits, no/odd/even parity, 1 or 2 stop bits |
| Defaults (Modbus) | 9600 bps, 8 data bits, no parity, 1 stop bit, slave address 1 |
| Defaults (BACnet) | 76800 bps, 8 data bits, no parity, MAC 1, device instance 1000 |
| Refresh / scan | I/O refresh 10 ms; Function Block scan 100 ms; watchdog approx. 3.2 s |
| Electrical and Mechanical | |
| Power supply | DC 24 V (21-28 V DC); supply must be >= 24 V for full analog accuracy |
| Power consumption | <= 3 W (24 V DC, no load); <= 5 W with all 3 relays energised |
| Dielectric withstand | 500 V DC for 1 min (power to communication terminals) |
| Isolation | Complete isolation between power supply, communication port and the 3 relay outputs |
| Operating / storage | -20 ~ +60 degC / -40 ~ +85 degC, 5-95 % RH non-condensing |
| Protection / mounting | IP20 (control cabinet), 35 mm DIN rail |
| Dimensions / weight | 88 x 107 x 59 mm (W x H x D), approx. 220 g |
| Housing / terminals | Flame-retardant ABS/PC (UL94-V0); screw terminals, 5.08 mm pitch, 0.2-2.5 mm2 |
Function Blocks
| Block | Function | Main parameters |
| PID | Closed-loop controller (P/I/D) | SP, Kp, Ti (0 = off), Td, dead zone, output bias, direct/reverse action, Ymin/Ymax |
| Scale | Linear range conversion | Input low/high, output low/high |
| High / Low Select | Selects the larger / smaller of two inputs | - |
| Two-Position | On/off control with threshold | ON value, OFF value |
| Compare | Threshold comparison, outputs 0/1 | Greater-than / less-than, threshold |
| AND / OR / NOT | Logic operations | - |
| Delay | On / off delay | On delay (s), off delay (s) |
| Buffer | Signal pass-through / relay | - |
Up to 16 blocks run in sequence on a 100 ms scan cycle; sources and targets can be universal inputs, internal points, analog outputs or relay outputs. When two blocks write the same output the interface raises a write-conflict warning before saving.
Web Configuration
- Connect the module RS485 terminals (A/B) to a PC through a USB-RS485 adapter.
- Double-click the RST key (or hold it while powering up) to enter Web configuration mode - the address LEDs flash all-on/all-off at 1 Hz.
- Set the PC network adapter to 192.168.5.1 / 255.255.255.0 and open http://192.168.5.2/ in a browser.
- Configure channel types and ranges, communication parameters, Function Blocks, then click Save to Flash.
All settings are written immediately and permanently stored by Save to Flash; firmware upgrade, configuration export/import and factory reset are performed from the same interface. The page supports English plus a second interface language, switchable in the top-right corner.
Installation and Wiring Highlights
Mount the module on a standard 35 mm DIN rail where the status LEDs and key are visible. Supply DC 24 V to terminals 24V+ / V- with correct polarity; connect the RS485 bus to B/A with shielded twisted pair and ground the shield at one point only. Universal input channels share the common terminals G1-G3 and each has a 3-pin jumper (J7-J12): pins 2-3 for 0-10 V / NTC-10K / dry contact, pins 1-2 for 4-20 mA - the jumper must match the configured channel type. Analog outputs M1-M3 use G3 as common; each relay output Dn/Qn is an isolated contact pair to be wired in series with the load and external supply.
Packing List
1 x PIOM-633 programmable I/O module (ordered model) | 1 x product certificate | 1 x user manual
OEM / ODM Customisation
As a manufacturer we support project-specific firmware: custom control logic and Function Block presets, PID defaults, protocol behaviour, channel naming, interface language packs, branding and packaging. Send us your I/O list and control sequence and we will come back with a configuration proposal.
FAQ
| What is the difference between PIOM-633-M and PIOM-633-B? | Both share the same hardware. PIOM-633-M works as a Modbus RTU slave (default 9600 bps, address 1); PIOM-633-B works as a BACnet MS/TP master node (default 76800 bps, MAC 1). The protocol is fixed at the factory per model. |
| Can it run PID control without an extra controller? | Yes. The Function Block engine runs inside the module, so PID, scaling, selection and interlock logic execute locally; the master station only reads and writes points. |
| Can I connect 4-20 mA sensors directly? | Yes - set the channel type to 4-20 mA and move that channel's jumper (J7-J12) to pins 1-2. Other channels stay at the factory position. |
| How do I configure and upgrade the module? | Over the RS485 port in Web configuration mode, from a browser at http://192.168.5.2/. Configuration files can be exported/imported and firmware upgraded online. |
| Do you support OEM/ODM and sample orders? | Yes. Sample orders, custom firmware, branding and packaging are all supported - please contact us with your application details. |
Compliance and Warranty
Designed and manufactured in compliance with CE (EMC) and RoHS requirements. Warranty: 12 months from purchase for quality-related faults under normal use (subject to the sales contract).