TFHV-SK-FVVMD-S3-CK-M Fan Coil Thermostat | 2-Pipe, Modbus RTU, EC Fan + PICV
TFHV-SK-FVVMD-S3-CK-M is an 86 mm two-pipe fan coil thermostat with room + coil dual-sensor cascade PI control, EC fan PWM and PICV 0-10 V or relay valve output, reporting over Modbus RTU RS-485.
TFHV-SK-FVVMD-S3-CK-M is an 86 × 86 mm fan coil unit (FCU) thermostat for two-pipe central air conditioning. A dual-sensor cascade PI controller — room loop plus coil loop — drives an EC fan through 0–10 V PWM and either a PICV 0–10 V proportional valve or a relay ON/OFF valve, and reports to the building management system over Modbus RTU RS-485.
Key Features
- 86 × 86 mm white glass panel, standard 86-type back box, IP20 indoor rating
- Segment LCD with clock, room temperature and relative humidity, mode and fan icons, auto-dimming backlight
- Six capacitive touch keys: POWER, MODE, BOOK, FAN, UP, DOWN
- Dual sensors: SHT4x digital temperature / humidity sensor (I²C) plus NTC coil temperature probe (12-bit ADC, 30-sample averaging)
- Cascade PI control — room PI outer loop (default 30 s) and coil PI inner loop (default 5 s), with automatic heating / cooling mode detection
- Valve output selectable by parameter P14: PICV 0–10 V (10 kHz PWM) or dry-contact relay for ON/OFF valves
- EC fan control: 0–10 V PWM, five manual speeds (30 / 45 / 60 / 80 / 100 %) plus automatic modulation from 30 to 100 %
- Safety and comfort: frost protection, over-heat cut-off at 55 °C coil temperature, sensor-fault fallback, keypad lock and occupancy control (door contact or radar) with unoccupied setpoints
- RTC with power-loss retention, daily timer, ten buzzer tones
- Two-pipe system; the four-pipe framework is reserved for future models
Specifications
| Model | TFHV-SK-FVVMD-S3-CK-M |
| Application | Fan coil unit (FCU), two-pipe |
| Display | Segment LCD (TM1621B driver), backlight with automatic dimming |
| Operating keys | Six capacitive touch keys |
| Sensors | SHT4x temperature / humidity; NTC coil temperature (S3: room + coil + humidity) |
| Control | Cascade PI (room + coil loops), 0.5 °C setpoint steps |
| Valve output | PICV 0–10 V (10 kHz PWM) or relay dry contact, selected by parameter P14 |
| Fan output | EC fan 0–10 V PWM, five speeds plus automatic modulation |
| Power supply | 90–265 VAC, 50/60 Hz (high-voltage version; internal logic 5 V DC) |
| Communication | Modbus RTU, RS-485 |
| Registers | 48 holding registers (40001–40048), function codes 03 / 06 |
| Baud rate | 9600 bps default; 19200 / 38400 selectable; 8-N-1 |
| Station address | 1–247 |
| Wiring | Shielded twisted pair, single-point earth at the controller |
| Working environment | −10 to +60 °C; ≤90 % RH, non-condensing |
| Storage | −20 to +85 °C |
| Protection | IP20 (indoor) |
| Dimensions | 86 × 86 mm; standard 86-type mounting box |
| Housing | White glass front, flame-retardant plastic base |
| Timer | Real-time clock with power-loss retention, daily schedule |
| Warranty | 12 months |
Model Code
The model code follows the company thermostat naming standard (WI-TS-001):
| Segment | Meaning |
TFHV |
Fan coil thermostat, high voltage (90–265 VAC) |
S |
Segment LCD display |
K |
Key operation |
FV |
EC fan, 0–10 V stepless speed control |
VM |
0–10 V pressure-independent control valve (PICV) |
D |
Two-pipe system |
S3 |
Room + coil temperature + humidity sensors |
C |
Clock display |
K |
Keypad lock |
M / Z |
Modbus RTU / ZigBee networking |
Modbus Interface
The thermostat is a Modbus RTU slave on RS-485 with 48 holding registers. Register 0 is the station address (1–247), register 1 sets 9600 / 19200 / 38400 bps, registers 2–6 carry power, mode, fan speed and the cooling / heating setpoints (×10), registers 7–9 return room temperature, coil temperature and humidity (×10), and registers 25–47 expose the internal parameters P01–P26.
Applications
Hotel guest rooms, offices, apartments, shopping centres and other fan coil terminals. The Modbus version suits buildings with an existing Modbus backbone, where wireless is not wanted.
Installation
Mount on a standard 86-type back box at 1.4–1.5 m above floor level, away from direct sunlight, heat sources and air outlets. Terminals: VCC, GND, RS-485 A / B, cold valve, hot valve, fan PWM, fan signal ground and door-contact input. Power and signal wiring must be de-energised while terminating.
Ordering
| Order code | Description |
| TFHV-SK-FVVMD-S3-CK-M | Modbus RTU, two-pipe, EC fan + PICV |
OEM / ODM: custom logo, panel colour, packaging and firmware options are available. Each unit ships with M4 mounting screws, a terminal identification card and a quick installation guide.