Basic Properties
Country Of Origin
Shenzhen, China
Brand Name
Matinal
PRODUCT MODEL
TFHV-SK-FVVMD-S3-CK-M
Trading Properties
MOQ
5 Pieces
Unit Price
US$52 - 62 / Piece
Payment Method
T/T
Product Summary

TFHV-SK-FVVMD-S3-CK-M is an 86 mm two-pipe fan coil thermostat with room + coil dual-sensor cascade PI control, EC fan PWM and PICV 0-10 V or relay valve output, reporting over Modbus RTU RS-485.

Product Description

TFHV-SK-FVVMD-S3-CK-M is an 86 × 86 mm fan coil unit (FCU) thermostat for two-pipe central air conditioning. A dual-sensor cascade PI controller — room loop plus coil loop — drives an EC fan through 0–10 V PWM and either a PICV 0–10 V proportional valve or a relay ON/OFF valve, and reports to the building management system over Modbus RTU RS-485.

Key Features

  • 86 × 86 mm white glass panel, standard 86-type back box, IP20 indoor rating
  • Segment LCD with clock, room temperature and relative humidity, mode and fan icons, auto-dimming backlight
  • Six capacitive touch keys: POWER, MODE, BOOK, FAN, UP, DOWN
  • Dual sensors: SHT4x digital temperature / humidity sensor (I²C) plus NTC coil temperature probe (12-bit ADC, 30-sample averaging)
  • Cascade PI control — room PI outer loop (default 30 s) and coil PI inner loop (default 5 s), with automatic heating / cooling mode detection
  • Valve output selectable by parameter P14: PICV 0–10 V (10 kHz PWM) or dry-contact relay for ON/OFF valves
  • EC fan control: 0–10 V PWM, five manual speeds (30 / 45 / 60 / 80 / 100 %) plus automatic modulation from 30 to 100 %
  • Safety and comfort: frost protection, over-heat cut-off at 55 °C coil temperature, sensor-fault fallback, keypad lock and occupancy control (door contact or radar) with unoccupied setpoints
  • RTC with power-loss retention, daily timer, ten buzzer tones
  • Two-pipe system; the four-pipe framework is reserved for future models

Specifications

Model TFHV-SK-FVVMD-S3-CK-M
Application Fan coil unit (FCU), two-pipe
Display Segment LCD (TM1621B driver), backlight with automatic dimming
Operating keys Six capacitive touch keys
Sensors SHT4x temperature / humidity; NTC coil temperature (S3: room + coil + humidity)
Control Cascade PI (room + coil loops), 0.5 °C setpoint steps
Valve output PICV 0–10 V (10 kHz PWM) or relay dry contact, selected by parameter P14
Fan output EC fan 0–10 V PWM, five speeds plus automatic modulation
Power supply 90–265 VAC, 50/60 Hz (high-voltage version; internal logic 5 V DC)
Communication Modbus RTU, RS-485
Registers 48 holding registers (40001–40048), function codes 03 / 06
Baud rate 9600 bps default; 19200 / 38400 selectable; 8-N-1
Station address 1–247
Wiring Shielded twisted pair, single-point earth at the controller
Working environment −10 to +60 °C; ≤90 % RH, non-condensing
Storage −20 to +85 °C
Protection IP20 (indoor)
Dimensions 86 × 86 mm; standard 86-type mounting box
Housing White glass front, flame-retardant plastic base
Timer Real-time clock with power-loss retention, daily schedule
Warranty 12 months

Model Code

The model code follows the company thermostat naming standard (WI-TS-001):

Segment Meaning
TFHV Fan coil thermostat, high voltage (90–265 VAC)
S Segment LCD display
K Key operation
FV EC fan, 0–10 V stepless speed control
VM 0–10 V pressure-independent control valve (PICV)
D Two-pipe system
S3 Room + coil temperature + humidity sensors
C Clock display
K Keypad lock
M / Z Modbus RTU / ZigBee networking

Modbus Interface

The thermostat is a Modbus RTU slave on RS-485 with 48 holding registers. Register 0 is the station address (1–247), register 1 sets 9600 / 19200 / 38400 bps, registers 2–6 carry power, mode, fan speed and the cooling / heating setpoints (×10), registers 7–9 return room temperature, coil temperature and humidity (×10), and registers 25–47 expose the internal parameters P01–P26.

Applications

Hotel guest rooms, offices, apartments, shopping centres and other fan coil terminals. The Modbus version suits buildings with an existing Modbus backbone, where wireless is not wanted.

Installation

Mount on a standard 86-type back box at 1.4–1.5 m above floor level, away from direct sunlight, heat sources and air outlets. Terminals: VCC, GND, RS-485 A / B, cold valve, hot valve, fan PWM, fan signal ground and door-contact input. Power and signal wiring must be de-energised while terminating.

Ordering

Order code Description
TFHV-SK-FVVMD-S3-CK-M Modbus RTU, two-pipe, EC fan + PICV

OEM / ODM: custom logo, panel colour, packaging and firmware options are available. Each unit ships with M4 mounting screws, a terminal identification card and a quick installation guide.

Compliance

CE and RoHS compliance activities are in progress. Please confirm the current certificate status for your project before ordering.