TFHV-SK-FVVMD-S3-CK-Z Fan Coil Thermostat | 2-Pipe, ZigBee, EC Fan + PICV
TFHV-SK-FVVMD-S3-CK-Z is the wireless version of the 86 mm two-pipe fan coil thermostat: room + coil dual-sensor cascade PI control, EC fan PWM and PICV or relay valve output, on a ZigBee 2.4 GHz link.
TFHV-SK-FVVMD-S3-CK-Z is an 86 × 86 mm fan coil unit (FCU) thermostat for two-pipe central air conditioning. A dual-sensor cascade PI controller — room loop plus coil loop — drives an EC fan through 0–10 V PWM and either a PICV 0–10 V proportional valve or a relay ON/OFF valve, and reports to the building management system over a ZigBee 2.4 GHz wireless link.
Key Features
- 86 × 86 mm white glass panel, standard 86-type back box, IP20 indoor rating
- Segment LCD with clock, room temperature and relative humidity, mode and fan icons, auto-dimming backlight
- Six capacitive touch keys: POWER, MODE, BOOK, FAN, UP, DOWN
- Dual sensors: SHT4x digital temperature / humidity sensor (I²C) plus NTC coil temperature probe (12-bit ADC, 30-sample averaging)
- Cascade PI control — room PI outer loop (default 30 s) and coil PI inner loop (default 5 s), with automatic heating / cooling mode detection
- Valve output selectable by parameter P14: PICV 0–10 V (10 kHz PWM) or dry-contact relay for ON/OFF valves
- EC fan control: 0–10 V PWM, five manual speeds (30 / 45 / 60 / 80 / 100 %) plus automatic modulation from 30 to 100 %
- Safety and comfort: frost protection, over-heat cut-off at 55 °C coil temperature, sensor-fault fallback, keypad lock and occupancy control (door contact or radar) with unoccupied setpoints
- RTC with power-loss retention, daily timer, ten buzzer tones
- Two-pipe system; the four-pipe framework is reserved for future models
Specifications
| Model | TFHV-SK-FVVMD-S3-CK-Z |
| Application | Fan coil unit (FCU), two-pipe |
| Display | Segment LCD (TM1621B driver), backlight with automatic dimming |
| Operating keys | Six capacitive touch keys |
| Sensors | SHT4x temperature / humidity; NTC coil temperature (S3: room + coil + humidity) |
| Control | Cascade PI (room + coil loops), 0.5 °C setpoint steps |
| Valve output | PICV 0–10 V (10 kHz PWM) or relay dry contact, selected by parameter P14 |
| Fan output | EC fan 0–10 V PWM, five speeds plus automatic modulation |
| Power supply | 90–265 VAC, 50/60 Hz (high-voltage version; internal logic 5 V DC) |
| Communication | ZigBee 2.4 GHz (IEEE 802.15.4) |
| Network | Joins a ZigBee coordinator for central supervision and point mapping |
| Wiring | No control cable between thermostat and plant; mains feed only |
| Fallback | Local control continues if the wireless link drops |
| Working environment | −10 to +60 °C; ≤90 % RH, non-condensing |
| Storage | −20 to +85 °C |
| Protection | IP20 (indoor) |
| Dimensions | 86 × 86 mm; standard 86-type mounting box |
| Housing | White glass front, flame-retardant plastic base |
| Timer | Real-time clock with power-loss retention, daily schedule |
| Warranty | 12 months |
Model Code
The model code follows the company thermostat naming standard (WI-TS-001):
| Segment | Meaning |
TFHV |
Fan coil thermostat, high voltage (90–265 VAC) |
S |
Segment LCD display |
K |
Key operation |
FV |
EC fan, 0–10 V stepless speed control |
VM |
0–10 V pressure-independent control valve (PICV) |
D |
Two-pipe system |
S3 |
Room + coil temperature + humidity sensors |
C |
Clock display |
K |
Keypad lock |
M / Z |
Modbus RTU / ZigBee networking |
Wireless Interface
The ZigBee version replaces the RS-485 control cable with a 2.4 GHz ZigBee link. Room temperature, setpoint, mode, fan speed and valve / fan outputs are exposed as wireless points and mapped into the central system by the site integrator; local operation continues if the link drops.
Applications
Hotel guest rooms, offices, apartments, shopping centres and other fan coil terminals. The ZigBee version suits buildings where per-room units must be supervised centrally without new control cabling.
Installation
Mount on a standard 86-type back box at 1.4–1.5 m above floor level, away from direct sunlight, heat sources and air outlets. Terminals: VCC, GND, cold valve, hot valve, fan PWM, fan signal ground and door-contact input. Power and signal wiring must be de-energised while terminating.
Ordering
| Order code | Description |
| TFHV-SK-FVVMD-S3-CK-Z | ZigBee, two-pipe, EC fan + PICV |
OEM / ODM: custom logo, panel colour, packaging and firmware options are available. Each unit ships with M4 mounting screws, a terminal identification card and a quick installation guide.
Compliance
CE and RoHS compliance activities are in progress. Please confirm the current certificate status for your project before ordering.