EDGE10 Controller | 10-Point IP Edge Controller for Niagara 4
EDGE10 is a 10-point IP-based field equipment controller that runs the Niagara 4 framework at the edge. It combines 5 universal inputs, 2 analogue outputs and 3 triac digital outputs with two daisy-chainable Ethernet ports and one RS-485 port, and integrates over BACnet/IP, BACne
The EDGE10 (Niagara Edge 10) is an IP-based field equipment controller powered by the Niagara Framework. It runs the full Niagara 4 stack at the edge with 10 points of on-board I/O, so small plant such as fan coil units, zone temperature control, single-stage air handling units and water-source heat pumps can be controlled, supervised and trended without installing a full JACE at every location.
Key Features
- Full Niagara 4 stack at the edge – Niagara 4.7 or later, with built-in web server, trending, alarms, data logging and real-time programming
- 10 points of on-board I/O – 5 universal inputs, 2 analogue outputs and 3 triac digital outputs
- Deterministic control – the built-in ACE engine runs wire-sheet applications with fast start-up to control time and deterministic I/O timing
- Two 10/100 Ethernet ports – daisy-chain controllers to continue network connectivity and avoid separate cabling back to a switch
- Open protocol connectivity – BACnet/IP, Modbus TCP and SNMP over the IP network; BACnet MS/TP and Modbus RTU over RS-485
- IO-R expansion – add 2 × IO-R-34 or 4 × IO-R-16 modules on a shielded RS-485 bus
- Licensed for 3 devices and 50 total points; 2 GB eMMC storage, real-time clock and secure boot
- DIN rail or panel mounting, 24 V AC/DC supply, certified to CE, FCC Part 15 Class B, UL916 and RoHS2
Specifications
| Parameter | Value |
|---|---|
| Product type | IP-based field equipment controller (Niagara Framework) |
| Model | EDGE-10 / Niagara Edge 10 |
| Platform | Niagara 4.7 or later, full Niagara stack with ACE deterministic engine |
| Universal inputs | 5 × UI: Type 3 (10K) thermistor, 0–100 kΩ, 0–10 VDC, 0–20 mA with external resistor, dry contact |
| Analogue outputs | 2 × AO: 0–10 VDC, 4 mA maximum output current |
| Digital outputs | 3 × DO: Triac, 24 VAC @ 0.5 A |
| Ethernet | 2 × 10/100 Mbps, daisy-chain capable |
| Serial port | 1 × RS-485 (BACnet MS/TP, Modbus RTU) |
| IP protocols | BACnet/IP, Modbus TCP, SNMP |
| Point capacity | 10 on-board points; licence for 3 devices and 50 total points |
| Expansion | 2 × IO-R-34 or 4 × IO-R-16 over shielded RS-485 (IO-R-16 requires a separate supply) |
| Processor / memory | iMX6 SoloX2 800 MHz ARM Cortex-A9/M4; 512 MB DDR SDRAM; 2 GB eMMC (1 GB user space) |
| Power supply | 24 V AC/DC |
| Mounting | EN50022 7.5 × 35 mm DIN rail or panel mounting |
| Operating environment | −20 to +60 °C; 5–95% RH, non-condensing |
| Storage environment | −40 to +85 °C; shipping and vibration ASTM D4169 Assurance Level II |
| Certifications | FCC Part 15 Class B, CE, C-UL, UL916 Open Energy Management Class 2, RoHS2, REACH, WEEE, CAN/CSA-C22.2 No. 205-12 |
| MTBF | 10 years |
Applications
Zone temperature control, fan coil units, single-stage air handling units, water-source heat pumps, roof-top units, and small sites without a building management system (retail chains, schools) where operational data has to be collected and brought into a supervisor.
Supply and Support
Supplied with Niagara N4 plus BACnet, Modbus and SNMP drivers. Software updates released for commercial use during the life of N4 are included; later major versions are not. System integrators and OEM partners: contact us for licence, spare and volume terms.